Technical details for Zinc

Physical properties of VM ZINC

Density: 7.18+ 0.02 g/cm³

Expansion of VM ZINC

Any work involving VM ZINC must allow it to expand and contract freely. The linear expansion of VM ZINC is 0.022 mm per meter and per degree centigrade.

Example:

In United Kingdom and the Republic of Ireland, the temperature range to bear in mind is from - 20°C in mid-winter to + 80°C on the surface of the metal in the sun at the height of the summer. Assuming an ambient temperature of 20°C during installation, we have to take into account:

  1. An additional 60°C (expansion)

  2. 40°C less (contraction)

For a 10 meter long panel:

anticipate an 0.022 mm x 10 x 60 = 13.2 mm increase in length

anticipate 0.022 mm x 10 x 40 = 8.8 mm contraction.


Working VM ZINC

To avoid micro-cracks in the VM ZINC to the right of the folds, do not work it when the temperature of the metal is below 7°C.

Ventilation of VM ZINC - Roofing and cladding

Contact with the outside air provides the CO2 required to form the natural patina of VM ZINC.

Without the presence of outside air VM ZINC does not protect itself and if there is any condensation, a chemical reaction can occur. As a result there can be corrosion on the underside of the VM ZINC which is not visible until holes appear on the outer skin.

Therefore, to ensure the durability of VM ZINC fixed on roof boarding its underside must be ventilated.


The best ventilation is ensured by two continuous air inlets: one at the bottom and the other at the top of the roof slope or cladding.

For installation on roof boarding, the underside of the latter and thus the underside of the VM ZINC will be ventilated. If it is impossible to realise this type of ventilation, it must be replaced by another air inlet system such as roof ventilators (slopes > 21°) or air vents. These air inlets are to be carefully spaced to ensure that the entire underside of the metal is ventilated.


Fixing fine mesh (<2 mm) to all the air inlets will deter insects, rodents and birds from entering.

The minimum depth of the air space under the roof boarding must be 40 mm. The total area of the air inlets (eaves and ridge) is 1/1,000th of the surface area of the roof, with a minimum width of 10 mm in the case of continuous ventilation.

In general we advise planning a total area for ventilation at the ridge that is 1.5 times greater than at the base of the roof. For slopes greater than 13 m long, intermediate air inlets should be planned for.

In most cases, a layer of insulating material is placed below the ventilated space. In order to avoid the risk of poorly installed insulation obstructing the air space, or of the insulation getting wet as the result of condensation, a breather membrane is required on the top side of the insulation. This breather membrane must be vapour permeable and end in the gutter, the box gutter or on the outside of the building.

This breather membrane can also prevent convection currents of (cold) outside air entering the building.

Given the increasing level of insulation in buildings, the installation of an effective vapour control layer on the warm side of the insulation is required.

The use of "PLUS" type VM ZINC the underside of which has already been protected during production, means that installation can be done without ventilation of the underside (Natural VM ZINC PLUS, QUARTZ-ZINC PLUS or ANTHRA-ZINC PLUS).

Compatibility of glues and mastics with VM ZINC

If less traditional decking is used (e.g. wood panels), the compatibility of all the decking's components with VM ZINC (e.g. glues) should be checked, and, if applicable, the possibility of ventilating the under-surface of the VM ZINC

Use of wood above VM ZINC

Incompatible wood varieties may not be used above VM ZINC elements (e.g. weather-boarding with incompatible boards or panels above the VM ZINC). Incompatible timber wash, treatment products or tanic acids will quickly attack the zinc and cause the formation of unattractive stains.

Forbidden Contacts

Direct contact with products such as fresh concrete, plaster, bitumen, mortar and structures containing substances that are aggressive towards VM ZINC.

Contact with metals such as copper, unprotected or ungalvanised iron, natural lead is forbidden. Only galvanised steel, natural lead protected by a patinating oil, FLEXUM lacquered lead, aluminium and austenitic steel can come in contact with VM ZINC.

Heating oil soot resulting from imperfect combustion landing on the zinc causes irreparable damage. Regular maintenance of furnace burners and the use of fuel that meets standards prevent this damage.

Using chimney "caps" may lead to aggressive deposits on the VM ZINC.

Use of an uncovered finishing cone is therefore recommended for fuel oil heating chimneys.

Before Installing VM ZINC

The roofer must ensure that:

  1. the structure is dry, clean and free of any rubbish (nails, leaves, vegetation, etc.)
  2. The roof timber nails are countersunk in order to avoid any contact with the VM ZINC.
  3. The screws are countersunk into the wooden substrate to avoid any contact with the VM ZINC.
  4. The structure conforms (flatness, compatibility, etc.) to the specifications.

Transportation and storage of profiled VM ZINC

VM ZINC must be transported and stored in dry conditions and in a constant temperature in order to avoid the formation of white rust.

White rust forms on the surface of VM ZINC when the latter comes in contact with humidity in the absence of carbon dioxide. In this case, the protective layer cannot form and white rust appears on the surface.

Unlike the patined layer, white rust provides no protection and leaves unattractive, indelible marks on the roof or facade. Consequently, we do not recommend installing panels that have been attacked by white rust.

Removing the protective film from pre-weathered zinc

As a general rule, the film must be removed from the entire surface at the same time, immediately following the installation of VM ZINC.

Exceptions to this rule:

  1. Roofs: when the roofer still has to walk on it to install flashings.

  2. Roofs: when people still have to walk on it to do other work such as masonry, joint filling, rendering walls, installing windows, safety equipment, lighting equipment, etc.

  3. Facades: when the cladding is close to the ground and there is still work to be done around it, etc. Under no circumstances must the film be left on installed VM ZINC for more than a month.

Surface appearance

Pre-weathered QUARTZ-ZINC and ANTHRA-ZINC are produced using a surface treatment on Natural VM ZINC. As with all patinas, this change in the crystalline structure of both surfaces of the metal evolves with time. The pre-weathering treatment completed at the plant gradually evolves and coalesces over time with the naturally formed zinc patina.

To ensure a consistent finish we recommend profiling and installing the components of a new project using a parent coil.

Moving around on the VM ZINC during and after installation on the roof

As a general rule, moving around on already installed VM ZINC, is to be avoided even if the latter is protected by film. As stated in the section on crimping, it is preferable to crimp the panels as they are installed. This also avoids unnecessary traffic on the panels that have already been laid.

However, if it is necessary to walk on the zinc, we strongly advise moving around using specially designed ladders and wearing safety shoes made for slippery surfaces as Natural VM ZINC, bilacquered VM ZINC and pre-weathered VM ZINC are slippery whether they are covered by film or not, particularly when they are wet.

In any case, obey the building site safety standards in force and as a minimum make sure you are always secured by a safety harness.

The VM ZINC fitted should be protected during peripheral works (rough casting, tuck-pointing, rendering, etc). However, this protection must allow effective ventilation of the upper surface of the VM ZINC.